CEN/TS 17889:2024

District heating pipes - Factory made flexible pipe systems - Classification, requirements and test methods for bonded or non-bonded system with thermoplastic reinforced service pipes (TRSP)

ACTIVE

About this standard

Languages
English and French
Type
NBN
Standards committee
CEN/TC 107
Status
ACTIVE
Publication date
20 November 2024
ICS Code
23.040.07 (Pipelines and its parts for district heat)
Withdrawn Date
Price
€ 121,00

About this training

Summary

This document specifies classification, general requirements and test methods for flexible, factory made, buried district heating pipe systems with thermoplastic reinforced service pipes (TRSP).
The factory made bonded or non-bonded flexible pipe systems, covered by this document, consists of:
- Thermoplastic reinforced service pipe, which consists of an inner layer made of PE-Xa, a thermoplastic intermediate layer, a reinforcement layer made of para-aramid fibres, an outer thermoplastic layer and a diffusion barrier layer, all with bonded structure
- Thermal insulation layer
- Casing made of PE.
Depending on the temperature profile, this document is applicable to a maximum operating temperature of 115 °C and maximum operating design pressure up to 1,6 MPa.
The pipe systems are designed for a service life of at least 30 years.
This document does not apply to cover surveillance systems.
NOTE For higher temperatures or for the transport of other fluids, for example potable water, additional requirements and testing is needed. Such requirements are not specified in this document.
A guideline for testing the pipe assembly is given in Annex D.