NBN HD 603:2007/A1:2016

Distribution cables of rated voltage 0,6/1 kV

ACTIVE

About this standard

Languages
English
Type
NBN Electro
Standards committee
AGORIA-ICT/J00127
Status
ACTIVE
Publication date
26 October 2016
Withdrawn Date
Price
€ 20,00

About this training

Summary

This standard specifies the construction, dimensions and test requirements of unarmoured power cables with XLPE-insulation for rated voltage (Uo/ U) of 0,6/ 1 kV type 5A and complying with requirements specified in EN 13501-6 and EN 50575.
(a) Insulating material
The insulation covered by this standard shall consist of cross-linked polyethylene and correspond to Table 2A of HD 603-1 - type DIX 1
(b) Rated voltage
Uo/ U: 0,6/ 1 kV
Definitions: see HD 603-1 Subclause 2.3
Cables covered by this standard are suitable to categories A, B and C according to IEC 60183.
(c)Highest rated temperature for the different types of insulating compound
Normal operation 90 °C
(d) Sheathing material
Suitable to the highest rated conductor temperature. It shall consist of PVC and correspond to Table 4A, type DMV 2 in HD 603-1.