Non-ducted portable air-cooled air conditioners and air-to-air heat pumps having a single exhaust duct — Testing and rating for performance (ISO 18326:2018)
This document specifies the standard conditions for capacity and efficiency ratings of non-ductedportable air-cooled air conditioners having a single exhaust duct and non-ducted portable air-cooledheat pumps having a single exhaust duct. Such air conditioners and heat pumps may include anevaporatively cooled condenser cooled by air and the evaporation of:a) condensate collected from the evaporator b) external supplementary water stored in a supplementary water tank orc) both a) and b).This document also specifies the test methods for determining the capacity and efficiency ratings.This document applies to equipment that is factory-made, electrically driven and uses mechanicalcompression. This document is applicable to equipment utilizing one or more refrigeration systems.This document is not applicable to the rating and testing of the following:i) Water-source heat pumps or water-cooled air conditioners ii) Multi-split-system air conditioners and air-to-air heat pumps (see ISO 15042:2017 for the testing ofsuch equipment) iii) Individual assemblies not constituting a complete refrigeration system iv) Equipment using the absorption refrigeration cycle v) Ducted equipment (see ISO 13253:2017 for the testing of such equipment) vi) Evaporative coolers or any other cooling systems that are not of the vapour compression type vii) Dehumidifiers viii) Spot coolers.