NBN EN 50525-2-21:2011

Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (Uo/U) - Part 2-21: Cables for general applications - Flexible cables with crosslinked elastomeric insulation

ACTIVE

About this standard

Languages
English and French
Type
NBN Electro
Status
ACTIVE
Publication date
26 August 2011
Replaces
HD 22.12 S2:2007 HD 22.4 S4:2004 HD 22.16 S2:2007 HD 22.11 S2:2007 HD 22.10 S2:2007
Corrected By
NBN EN 50525-2-21:2011
ICS Code
29.060.20 (Cables)
Withdrawn Date
Price
€ 163,00

About this training

Summary

EN 50525-2-21 applies to flexible cables, insulated with crosslinked elastomeric compound, and sheathed with either crosslinked elastomeric compound or thermoplastic polyurethane (TPU). The cables are of rated voltages U0/ U up to and including 450/ 750 V. The cables are intended for a variety of applications where appliances or equipment, including heavy industrial equipment, require a flexible connection to the power supply. The maximum conductor operating temperatures for the cables in this standard are 60 °C (R types), 90 °C (B types) and 110 °C (G types). The following particular cable types are included: - General purpose cables (RR and RN types) - Water-resistant cables (RN8 types) - General purpose cables (BB and BN4 types) - TPU sheathed cables (BQ types) - Heat resistant cables (GG types) NOTE HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-2-21 should be read in conjunction with EN 50525-1, which specifies general requirements.